Electric Motor Selection: How to Size a Motor for Industrial Equipment
What size motor does your equipment need? Horsepower is a starting point, but it won’t tell you if the motor can start a loaded conveyor or run a mixer through repeated production cycles. Electric motor selection starts with the load, then works through speed, torque, duty cycle and installation requirements. Here’s how to put those pieces together.
Start Motor Selection with the Driven Equipment
Before choosing a motor, identify the equipment’s required shaft speed and torque across normal operation, startup and peak loading.
Different machines place different demands on the motor:
- Centrifugal pumps and fans: Torque generally increases with speed under comparable system conditions. Check the equipment’s performance curve across the intended operating range.
- Conveyors: A loaded belt may require more torque to start than to keep moving.
- Mixers: Changing viscosity, batch size and material buildup can change the required torque.
Record how long the machine runs, how often it starts and how quickly it must accelerate. For a replacement motor, review why the original failed. Repeating its nameplate rating may repeat the same problem.
Use the Motor Torque Formula to Calculate Shaft Power
The motor torque formula relates mechanical horsepower, shaft speed and torque:
Torque (lb-ft) = (Horsepower × 5,252) ÷ Speed (RPM)
For a motor power calculation using torque and speed:
Horsepower = (Torque × RPM) ÷ 5,252
For metric units:
Power (kW) = (Torque in N·m × RPM) ÷ 9,550
Use torque and speed at the same shaft. If a gearbox or belt drive connects the motor to the equipment, account for the power transmission system’s ratio and efficiency.
These equations describe running power. They do not calculate breakaway torque or acceleration requirements.
Electric Motor Sizing Example
Assume a directly coupled machine requires 60 lb-ft of running torque at 1,750 RPM:
Required horsepower = (60 × 1,750) ÷ 5,252 = 19.99 HP
The calculated running requirement is approximately 20 HP. Final motor selection still depends on startup demands, load variations and operating conditions.
Motor horsepower describes mechanical output. To estimate electrical input at an assumed 92% motor efficiency:
Electrical input = (19.99 × 0.746) ÷ 0.92 = 16.2 kW
This excludes drive losses. It also does not size wiring, overload protection or a VFD.
Check Starting Torque and Duty Cycle
A motor can have enough running horsepower and still struggle to accelerate the load. Available motor torque must exceed load torque during acceleration, with enough margin to reach operating speed within the motor’s thermal limits. For pumping applications, comparing pump and motor torque-speed curves helps verify that capability.
High inertia and frequent starts increase heating. Reversing, jogging and repeated heavy cycles may require a different motor design or rating than continuous operation.
Avoid treating service factor as an automatic allowance for normal production loads. Confirm the manufacturer’s permitted conditions before using it.
Match the Motor to the Installation and Controls
Complete electric motor selection by checking:
- Power supply: Voltage, phase and frequency, plus compatibility with the starting method.
- Mechanical fit: Frame size, mounting, shaft dimensions and allowable shaft loads.
- Environment: Ambient temperature, altitude, moisture, dust and corrosive exposure. Hazardous locations require the appropriate certification; a TEFC enclosure alone does not provide it.
- Speed control: For variable frequency drive operation, verify the motor’s permitted speed and torque range. Shaft-mounted fans provide less cooling at reduced speed, which can limit continuous torque.
Select the motor and drive together when speed varies. The motor’s full-load current and overload demands must fit the drive’s ratings.
Find the Right Industrial Motor with DXP
Have a new application or a motor that keeps giving you trouble? Bring us the load requirements, operating schedule and installation details. We can help evaluate the equipment and the conditions it needs to handle.
DXP supplies electric motors in multiple sizes, enclosures, voltage ratings and configurations, along with power transmission components and controls. Our service and repair network also supports existing rotating equipment.
Contact DXP for help selecting a motor for your next installation or replacement.